H07ZZ-F
Cables For Wind Farms / H07ZZ-F
H07ZZ-F
These cables are designed for indoor and outdoor installation, particularly for applications where only small quantities of smoke and corrosive gases may be emitted in the event of a fire.
STRUCTURE & SPECIFICATION
Standard | EN 50525-3-21 |
Conductor material | copper, bare |
Conductor class | class 5 = fine stranded |
Insulation | rubber EI8 |
Sheathing material | rubber (EPR) EM8 |
Flame-retardant | VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C) |
Smoke density | DIN EN 61034/IEC 61034 |
Halogen-free | DIN EN 50267/IEC 60754 |
UV-resistant | yes |
For outdoor use | yes |
Maximum permitted conductor temperature, °C | 90 °C |
Permitted outer cable temperature, fixed, °C | -40 - +70 °C |
Permitted outer cable temperature, in motion/during installation, °C | -5 - +70 °C |
Nominal voltage Uo | 450 V |
Nominal voltage U | 750 V |
Core identification | colours acc. to VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers |
Colour of outer sheath | black |