Single core cables are used in short lengths, e.g. for the connection of switchgear cubicles and for the connection of mobile transformer substations. When laying and during operation, care should be taken to protect them from excessive mechanical stress. The outer semi-conducting layer must not be heated before removal.
STRUCTURE & SPECIFICATION
Standard | VDE 0250-813 (with ref. to) |
Conductor material | tinned copper |
Conductor class | class 5 = fine stranded |
Insulation | rubber 3GI3 |
Electrical field control | inner and outer semiconducting rubber layer |
Arrangement of protective conductors | copper spiral shield on each core |
Torsion | +/- 25 °/m |
Sheathing material | rubber (CR) 5GM3 |
Colour outer sheath | red |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
Oil-resistant | EN 60811-404 |
Ozone-resistant | yes |
For outdoor use | yes |
Maximum permitted conductor temperature, °C | 90 °C |
Permitted outer cable temperature, fixed, °C | -40 - +80 °C |
Permitted outer cable temperature, in motion/during installation, °C | -25 - +60 °C |
Bending radius, fixed installation | 6 x DA |
Bending radius, moving application | 10 x DA |
Core diameter | 10.1 mm |
Number of cores | 1 |